Humid air (moist air) from the ASHRAE RP-1485 real-moist-air formulation: this page gives the humidity ratio, thermodynamic wet-bulb temperature, dew point and specific enthalpy of moist air on a grid of dry-bulb 0–50 °C by relative humidity 10–100 %, at sea-level pressure (101.325 kPa). Humidity ratio and enthalpy are per kilogram of dry air.

Values are computed from CoolProp==6.6.0 - HAPropsSI real-moist-air formulation (ASHRAE RP-1485; Herrmann, Kretzschmar & Gatley, 2009). The grid covers dry-bulb 050 °C and relative humidity 10100 % at 101.325 kPa; the three psychrometric calculators handle other pressures.

Also known as
moist air, wet air, psychrometrics, humid air
Pressure
101.325 kPa (sea level)
Tabulated range
050 °C dry-bulb · 10100 % RH
Enthalpy datum

Moist-air specific enthalpy is given per kilogram of DRY air, on the ASHRAE reference state: the enthalpy of dry air and of liquid water are both zero at 0 degC. Enthalpy values from a table built on a different reference state are not directly comparable to these.

ASHRAE RP-1485 - Thermodynamic Properties of Real Moist Air, Dry Air, Steam, Water, and Ice (Herrmann, Kretzschmar & Gatley, 2009). Herrmann, S., Kretzschmar, H.-J. & Gatley, D.P. (2009), Thermodynamic Properties of Real Moist Air, Dry Air, Steam, Water, and Ice (RP-1485), HVAC&R Research 15(5). This is the reference real-gas moist-air formulation implemented by CoolProp's HAPropsSI, used to generate every grid value. https://www.ashrae.org/technical-resources/bookstore/ashrae-research-project-rp-1485

At 25 °C dry-bulb · 50 % RH
reference snapshot
Humidity ratio
9.93g/kg da
Wet-bulb temp
17.9°C
Dew point
13.9°C
Specific enthalpy
50.4kJ/kg da
Explore

Read a value at any dry-bulb and humidity

Move the sliders to interpolate between the tabulated grid points. The readout never goes outside the validated 050 °C and 10100 % range, and every number is interpolated from the committed table below — nothing is computed from a model in your browser. For another pressure, use the calculators.

Bilinearly interpolated from the tabulated grid — dry-bulb 050 °C and relative humidity 10100 %, at 101.325 kPa — never extrapolated. For another pressure, use the calculators.

25 °C
50 %
Humidity ratio
9.93 g/kg dry air
Specific enthalpy
50.4 kJ/kg dry air
Wet-bulb temp
17.9 °C
Dew point
13.9 °C

Humidity ratio is the mass of water vapour per kilogram of dry air; the wet-bulb temperature is what an evaporating thermometer reads; the dew point is the temperature at which this air would start to condense; and the specific enthalpy is its heat content per kilogram of dry air, on the dry-air/liquid-water 0 °C datum. Every value is interpolated from the committed grid below — nothing is computed from a model in your browser.

For a value at another pressure or to see the worked steps: wet-bulb temperature · dew point · humidity ratio & enthalpy.

Full tables

Every tabulated point

Rows are dry-bulb temperature (°C); columns are relative humidity (%). Humidity ratio and enthalpy are per kilogram of dry air; the wet-bulb and dew-point columns are temperatures. Every value is for 101.325 kPa.

Humidity ratio g/kg dry air
°C \ % RH102030405060708090100
00.380.751.131.511.892.272.653.033.413.79
50.541.081.622.162.703.243.794.334.885.42
100.761.522.283.043.814.585.346.126.897.66
151.052.113.174.235.306.377.458.539.6110.69
201.452.904.365.827.298.7710.2611.7513.2514.76
251.963.935.927.929.9311.9513.9916.0318.1020.17
302.635.287.9610.6513.3716.1218.8821.6824.4927.33
353.497.0210.5914.2017.8521.5525.2829.0632.8936.76
404.599.2413.9718.7723.6428.5833.6038.7043.8849.14
455.9812.0718.2824.6131.0737.6644.3951.2558.2665.42
507.7215.6323.7432.0640.6049.3658.3667.6077.1086.86
Wet-bulb temperature °C
°C \ % RH102030405060708090100
0-5.6-4.9-4.3-3.6-3.0-2.4-1.8-1.2-0.60.0
5-2.3-1.4-0.60.61.32.12.93.64.35.0
101.42.53.54.65.56.57.48.39.210.0
154.65.97.28.59.710.811.913.014.015.0
207.69.310.812.313.815.116.417.718.920.0
2510.412.514.416.217.919.521.022.423.725.0
3013.215.718.020.122.023.825.527.128.630.0
3515.918.921.523.926.128.230.131.833.535.0
4018.522.025.127.830.332.634.636.638.340.0
4521.225.228.731.834.537.039.241.343.245.0
5023.828.432.335.738.741.443.846.148.150.0
Dew-point temperature °C
°C \ % RH102030405060708090100
0-25.4-18.2-13.9-10.7-8.2-6.1-4.3-2.7-1.30.0
5-21.7-14.4-9.9-6.6-4.0-1.9-0.01.83.55.0
10-18.2-10.6-6.0-2.60.12.64.86.78.410.0
15-14.7-6.9-2.11.54.77.39.611.613.415.0
20-11.2-3.21.96.09.312.014.416.418.320.0
25-7.70.56.210.513.916.719.221.323.225.0
30-4.34.610.614.918.521.423.926.228.230.0
35-1.08.714.919.423.026.128.731.033.135.0
402.612.819.123.827.630.733.535.938.040.0
456.416.923.428.332.235.438.240.743.045.0
5010.120.927.732.736.740.143.045.647.950.0
Specific enthalpy kJ/kg dry air
°C \ % RH102030405060708090100
00.91.92.83.84.75.76.67.68.59.5
56.47.79.110.411.813.214.515.917.318.6
1012.013.915.817.719.621.623.525.527.429.4
1517.820.423.125.828.531.233.936.639.442.1
2023.827.531.234.938.642.446.149.953.757.6
2530.135.240.245.350.455.660.866.071.276.5
3036.943.750.557.464.471.478.485.692.8100.0
3544.253.262.471.681.090.5100.1109.7119.5129.5
4052.164.076.288.6101.1113.8126.7139.8153.2166.7
4560.776.592.5108.9125.6142.6159.9177.6195.7214.2
5070.390.8111.9133.4155.6178.3201.6225.5250.1275.4
Typical values

Moist-air properties at a glance

At 25 °C dry-bulb and 50 % relative humidity, the humidity ratio is 9.9 g/kg dry air, the wet-bulb temperature 17.9 °C, the dew point 13.9 °C and the specific enthalpy 50.4 kJ/kg dry air. At 35 °C dry-bulb and 80 % relative humidity, the humidity ratio is 29.1 g/kg dry air, the wet-bulb temperature 31.8 °C, the dew point 31.0 °C and the specific enthalpy 109.7 kJ/kg dry air. At 5 °C dry-bulb and 90 % relative humidity, the humidity ratio is 4.9 g/kg dry air, the wet-bulb temperature 4.3 °C, the dew point 3.5 °C and the specific enthalpy 17.3 kJ/kg dry air.

Sources

Where the numbers come from

Every value on this page is computed by a deterministic formulation — none is entered by hand. The generating method and the references it is checked against:

  • ASHRAE RP-1485 - Thermodynamic Properties of Real Moist Air, Dry Air, Steam, Water, and Ice (Herrmann, Kretzschmar & Gatley, 2009), the reference real-gas moist-air formulation
  • ASHRAE Handbook-Fundamentals, Chapter 1 (Psychrometrics) - sea-level psychrometric chart and moist-air saturation properties (cited validation values)
  • CoolProp 6.6.0 - HAPropsSI implementation of the ASHRAE RP-1485 moist-air formulation

Model: CoolProp==6.6.0 - HAPropsSI real-moist-air formulation (ASHRAE RP-1485; Herrmann, Kretzschmar & Gatley, 2009) · Generated 2026-06-07

The committed data file for this page is published as JSON on GitHub under CC BY 4.0.

Validation

Checked against cited values

The formulation is cross-checked against published ASHRAE psychrometric values — the canonical 25 °C / 50 % RH chart state and moist-air saturation properties — at a 1.0 % tolerance (chart/table-reading precision). The page is published only because every check passes.

Property / pointHumidity ratio · 25 °C · 50 % RH
Cited reference value9.9 g/kg dry air
Model computed9.9257 g/kg dry air
Error vs reference0.26% (tolerance 1%)

ASHRAE Handbook-Fundamentals, Psychrometrics chapter / Psychrometric Chart No. 1 (sea level). ASHRAE Handbook-Fundamentals, Chapter 1 (Psychrometrics), sea-level psychrometric chart No. 1: the canonical 25 degC dry-bulb / 50 % RH state has a humidity ratio of about 9.9 g per kg dry air. Tolerance 1.0 % reflects chart-reading precision. https://www.ashrae.org/technical-resources/ashrae-handbook

Property / pointWet-bulb temperature · 25 °C · 50 % RH
Cited reference value17.9 degC
Model computed17.883 degC
Error vs reference0.092% (tolerance 1%)

ASHRAE Handbook-Fundamentals, Psychrometrics chapter / Psychrometric Chart No. 1 (sea level). ASHRAE Handbook-Fundamentals, Chapter 1 (Psychrometrics), sea-level psychrometric chart No. 1: at 25 degC dry-bulb / 50 % RH the thermodynamic wet-bulb temperature is about 17.9 degC. Tolerance 1.0 % reflects chart-reading precision. https://www.ashrae.org/technical-resources/ashrae-handbook

Property / pointDew-point temperature · 25 °C · 50 % RH
Cited reference value13.9 degC
Model computed13.867 degC
Error vs reference0.238% (tolerance 1%)

ASHRAE Handbook-Fundamentals, Psychrometrics chapter / Psychrometric Chart No. 1 (sea level). ASHRAE Handbook-Fundamentals, Chapter 1 (Psychrometrics), sea-level psychrometric chart No. 1: at 25 degC dry-bulb / 50 % RH the dew-point temperature is about 13.9 degC. Tolerance 1.0 % reflects chart-reading precision. https://www.ashrae.org/technical-resources/ashrae-handbook

Property / pointSpecific enthalpy · 25 °C · 50 % RH
Cited reference value50.3 kJ/kg dry air
Model computed50.423 kJ/kg dry air
Error vs reference0.245% (tolerance 1%)

ASHRAE Handbook-Fundamentals, Psychrometrics chapter / Psychrometric Chart No. 1 (sea level). ASHRAE Handbook-Fundamentals, Chapter 1 (Psychrometrics), sea-level psychrometric chart No. 1: at 25 degC dry-bulb / 50 % RH the moist-air specific enthalpy is about 50.3 kJ per kg dry air (dry-air/liquid-water 0 degC datum). Tolerance 1.0 % reflects chart-reading precision. https://www.ashrae.org/technical-resources/ashrae-handbook

Property / pointHumidity ratio · 30 °C · 100 % RH
Cited reference value27.3 g/kg dry air
Model computed27.3329 g/kg dry air
Error vs reference0.12% (tolerance 1%)

ASHRAE Handbook-Fundamentals, Psychrometrics chapter - moist-air saturation properties (sea level). ASHRAE Handbook-Fundamentals, Chapter 1 (Psychrometrics), thermodynamic properties of moist air at saturation (sea level): saturated air at 30 degC holds about 27.3 g of water vapour per kg dry air. Tolerance 1.0 % reflects table/chart-reading precision. https://www.ashrae.org/technical-resources/ashrae-handbook

Property / pointHumidity ratio · 10 °C · 100 % RH
Cited reference value7.6 g/kg dry air
Model computed7.6626 g/kg dry air
Error vs reference0.824% (tolerance 1%)

ASHRAE Handbook-Fundamentals, Psychrometrics chapter - moist-air saturation properties (sea level). ASHRAE Handbook-Fundamentals, Chapter 1 (Psychrometrics), thermodynamic properties of moist air at saturation (sea level): saturated air at 10 degC holds about 7.6 g of water vapour per kg dry air. Tolerance 1.0 % reflects table/chart-reading precision. https://www.ashrae.org/technical-resources/ashrae-handbook

Limitations

Before you use these numbers

  • Real-moist-air psychrometric properties from CoolProp's HAPropsSI (ASHRAE RP-1485; Herrmann, Kretzschmar & Gatley, 2009) at sea-level pressure (101.325 kPa). The grid covers dry-bulb 0-50 degC in 5 deg steps and relative humidity 10-100 % in 10 % steps. Humidity ratio is per kg dry air; enthalpy is per kg dry air on the dry-air/liquid-water 0 degC datum. The formulation is not extrapolated beyond the tabulated ranges. Values are for preliminary design; verify for critical service.
  • Moist-air specific enthalpy is given per kilogram of DRY air, on the ASHRAE reference state: the enthalpy of dry air and of liquid water are both zero at 0 degC. Enthalpy values from a table built on a different reference state are not directly comparable to these.
  • The grid is for sea-level pressure (101.325 kPa) only. The three calculators handle other pressures (80-110 kPa). Dew-point and wet-bulb temperatures below 0 degC (the dry, cold corner of the grid) are reported by the formulation but sit outside the over-water range the companion TS engine validates; treat sub-zero dew/frost points as indicative.
  • Use for preliminary design; verify for critical service.